T10EM-24 Emergency T10 2ft 9/8/7w 5cct 120-277v Type B from RAB Lighting is a UL 924-certified Type B T8 tube with field-adjustable power and color temperature. Designed to replace traditional fluorescent linear tubes, this 2 ft T10 Linear Emergency lamp includes built-in lithium batteries for emergency lighting and provides 90 minutes of emergency operation.
Product Summary
- Product Type: T10 Linear Emergency
- Length: 2 ft
- Input Wattage: 9/8/7W; 7W default
- Voltage: 120-277V
- Color Temperature: 3000/3500/4000/5000/6500K
- Emergency Operation: 90 minutes
- Free shipping on orders over $250
Product Benefits
- Replaces traditional fluorescent linear tubes with a UL Type B, Ballast Bypass LED tube.
- Built-in lithium batteries provide emergency lighting backup when needed.
- Field-adjustable wattage and color temperature allow one lamp to support multiple lighting needs.
- Reduces maintenance and replacement costs with a 50,000-Hour LED lifespan.
Key Features
- Emergency backup: Built-in lithium batteries for emergency lighting with 90 minutes of emergency operation.
- Emergency output: 500lm @ 4000K.
- Field-adjustable wattage: 9/8/7W with 7W default.
- Field-adjustable CCT: 3000/3500/4000/5000/6500K with 4000K default.
- Type B installation: UL Type B, Ballast Bypass installation method.
- Dimmable: Dimmable down to 10% on compatible TRIAC/ELV dimming systems.
- Included accessories: Includes tombstones and test button.
- Durable enclosure: Constructed from frosted, shatter-resistant polycarbonate.
Specifications
Technical Specifications
| Product | T10EM-24 |
| UPC | 192552054157 |
| Product Type | T10 Linear Emergency |
| Wattage Equivalency | 17W Fluorescent |
| Input Wattage | 9/8/7W; 7W default |
| Driver | Constant Current 120-277V 50/60 Hz; 120V: 75mA; 208V: 43mA; 240V: 38mA; 277V: 33mA |
| THD | <20% |
| Power Factor | 0.9 |
| Dimmable | Yes, dimmable down to 10% on compatible TRIAC/ELV dimming systems. |
| Operating Temperature | -4°F to 113°F(-20 to 45°C) |
| Flicker | 50% |
Performance Specifications
| Lumens at 7W | 880lm @ 3000K; 920lm @ 3500K; 940lm @ 4000K; 940lm @ 5000K; 920lm @ 6500K |
| Lumens at 8W | 1000lm @ 3000K; 1050lm @ 3500K; 1100lm @ 4000K; 1100lm @ 5000K; 1050lm @ 6500K |
| Lumens at 9W | 1120lm @ 3000K; 1150lm @ 3500K; 1200lm @ 4000K; 1200lm @ 5000K; 1150lm @ 6500K |
| Efficacy at 7W | 126lm/W @ 3000K; 131lm/W @ 3500K; 134lm/W @ 4000K; 134lm/W @ 5000K; 131lm/W @ 6500K |
| Efficacy at 8W | 125lm/W @ 3000K; 131lm/W @ 3500K; 138lm/W @ 4000K; 138lm/W @ 5000K; 131lm/W @ 6500K |
| Efficacy at 9W | 124lm/W @ 3000K; 128lm/W @ 3500K; 133lm/W @ 4000K; 133lm/W @ 5000K; 128lm/W @ 6500K |
| L70 Lifespan | 50,000-Hour LED lifespan based on IES LM-70 results |
| Emergency Fixture Use | Yes, meets UL924 |
| Emergency Test Button | Included as accessory |
| Battery Type | Lithium |
| Emergency Operation | 90 minutes |
| Emergency Lumens | 500lm @ 4000K |
| Beam Angle | 140° |
| Color Temperature | Default: 4000K; Field adjustable via dip switch; 3000/3500/4000/5000/6500K |
| Color Accuracy | ≥80 CRI |
| R9 Value | High color performance with R9 greater than 0 |
| Color Consistency | <7-step (3500/4000/5000K); <5-step (3000/6500K) |
| Color Stability | LED color temperature is warrantied to Shift no more than 200K in color temperature over a 5-year period |
Physical Specifications
| Length | 2 ft |
| Shape | T10 Linear |
| Finish | White |
| Base Type | G13 |
| Endcap Material | Copper |
| Enclosure Material | Constructed from frosted, shatter-resistant polycarbonate |
| Lens Finish | Frosted |
| Maximum Mounting Height | 11.67ft (3.55m) |
| Minimum Luminaire Dimension with Max. No. of Tubes | 61 x 61 x 5 cm; 24 x 24 x 1.97 inch |
| LED Lamps Tested in Luminaire | 4 |
| Lamp Holder to Lamp Holder Spacing | 11 cm; 4.33 inch |
Compliance & Safety
| Installation Method | UL Type B, Ballast Bypass |
| Listings | UL Recognized, UL Classified |
| UL 924 | UL 924-certified |
| Environment | Suitable for use indoors in dry and damp environments. |
| Fixture Rating | Suitable for use in enclosed fixtures |
| DLC Listed | This product family is listed with the DesignLights Consortium (DLC). |
| Certification Model Number | T10307(T10EM-24) |
| California Title 20 Compliant | No |
| California Title 24 JA8 Compliant | No |
| California Energy Commission (CEC) Status | Lawful for Sales in California |
| IESNA LM-79 & LM-80 Testing | RAB LED luminaires and LED components have been tested by an independent laboratory in accordance with IESNA LM-79 and LM-80. |
| RoHS | Mercury and UV free. RoHS-compliant components. |
| FCC | Complies with Part 15 of the FCC Rules |
| Warranty | 5-Year, No-Compromise Warranty |
Applications
- General purpose lighting where a Type B T8 tube is required.
- Battery-powered backup LED lighting applications.
- Retrofitting traditional fluorescent linear tubes.
- Indoor dry and damp environments.
- Enclosed fixture applications.
Installation Tips
- Read carefully before installing lamps and retain the instructions for future reference.
- RAB lamps must be wired in accordance with the National Electrical Code and all applicable local codes.
- Proper grounding is required for safety.
- This product must be installed in accordance with the applicable installation code by a person familiar with the construction and operation of the product and the hazards involved.
- Disconnect power at the source before installation, inspection or removal. Do not simply switch off fixture.
- LED Retrofit Kit installation requires knowledge of luminaires electrical systems. If not qualified, do not attempt installation. Contact a qualified electrician.
- Do not use this retrofit kit in luminaires employing shunted bi-pin lampholders.
- Replace existing lamp holders with new non-shunted lamp holders to install with the EM924 led tube in the fixture.
- Slide the lamp ON/OFF switch to ON. Select desired watt and color temperature before power on.
- Rotate the tube until it locked. If the tube is not pushed in place, the lamp cannot be powered on and lit up.
- Install Emergency LED Tube and ensure test switch is installed and connected.
Frequently Asked Questions
What type of lamp is the T10EM-24?
The T10EM-24 is a T10 Linear Emergency lamp and a UL 924-certified Type B T8 tube with field-adjustable power and color temperature.
What wattage settings are available?
The input wattage is 9/8/7W, with 7W default.
What color temperatures can be selected?
The T10EM-24 is field adjustable via dip switch for 3000/3500/4000/5000/6500K, with 4000K default.
How long does emergency operation last?
The emergency operation is 90 minutes.
What is the emergency lumen output?
The emergency lumen output is 500lm @ 4000K.
What voltage does this lamp support?
The constant current driver supports 120-277V 50/60 Hz.
Is the T10EM-24 dimmable?
Yes. It is dimmable down to 10% on compatible TRIAC/ELV dimming systems.
What installation method does this lamp use?
The installation method is UL Type B, Ballast Bypass.
Can this lamp be used in enclosed fixtures?
Yes. The fixture rating is suitable for use in enclosed fixtures.
What routine emergency testing is recommended?
Monthly testing includes a 30-second discharge test by depressing the test button. Annual testing includes allowing a 24-hours charge before conducting a full 90-minute discharge test.